Compra e instalación de Generadores de Energía diesel, air cooled, 25kVA o POWER SOLUTIONS referencia P27D6

UNICEF
Compra e instalación de Generadores de Energía diesel, air cooled, 25kVA o POWER SOLUTIONS referencia P27D6 Request for proposal

Reference: RFQ2022-45 Generadores de Energía
Beneficiary countries or territories: Colombia
Registration level: Basic
Published on: 04-Nov-2022
Deadline on: 24-Nov-2022 23:59 (GMT -5.00)

Description

Propósito de la contratación
Compra e instalación de cincuenta (50) generadores de Energía diesel, air cooled, 25kVA, 60Hz o POWER SOLUTIONS referencia P27D6, nuevos -primer uso. b. Contexto
Compra Generadores de Energía diesel,air cooled, 25kVA, 60Hz, o POWER SOLUTIONS referencia P27D6 c. Objetivos y metas de la contratación
Se aceptarán generadores de dos características, descritas a continuación:
• Compra de 50 Generadores de Energía diesel, air cooled, 25kVA, 60Hz que cumplan con las siguientes características y estándares técnicos:
Generating Set skid mounted # 25 kVA (Model Deutz F3L91 2)
A complete diesel air cooled generator set including diesel engine, alternator, control panel, starting equipment, fuel tank and all other accessories for autonomous operation.
Factory test is available for any ordered units and all generators shall be in accordance with international standards.
Availability of internationally recognized certification for quality management such as ISO9001 and compliance with the following codes (or equivalent):
- UL 2200
- EPA emissions, stationary emergency, 40CFR60
- NFPA 110 capable
Construction and specification standards
The generator set is produced and performance specified according to the following standards (or equivalent):
- Directive EC/2006/42 on Machinery
- ISO 8528: Reciprocating internal combustion engine driven alternating current generating sets
- BS 5000-15:1980: Rotating electrical machines of particular types or for particular applications
- BS 5514-1:1996: Reciprocating internal combustion engines
- ISO 3046-1:1995: Reciprocating internal combustion engines
- BS 4999: General requirements for rotating electrical machines
- VDE 0530: Safety of electric motors
FEATURES
Rating: 25 kVA (20 kW)
The ratings are at (NTP) Normal Temperature and Pressure
Output ratings are prime Power in accordance with ISO 8528 e.g.
power available at variable load with no limitation on hours of operation and capable of 10% overload for 1 hour in ant 12 hours
Cos ö: 0.8 rit
Frequency: 60 Hz
Voltage: 220/127V+N
Three phase
Ambient conditions:
· Average year temperature #C30 °C
· Average 24 hours temperature 30 °C
· Minimum temperature - #C10 °C
· Maximum temperature 50 °C
The Generating Set is equipped with:
ENGINE
Deutz F3L91 2 air cooled having the following features:
Speed: 1.800 rpm
Speed Governor
Heavy duty air cartridge filter
Cartridge oil filter
Fuel Filter
Residential Silencer
Exhaust with suitable flexible piping
Starter: Electric Starter (including batteries leads & automatic battery charging equipment).
Integrated fuel tank having sufficient capacity to run the generator continuously for 8 hours at rated capacity. Tank have all necessary piping for operation and filling and conveniently positioned fuel level indicator.
ALTERNATOR
Stamford model PI 144E synchronous, air cooled, three phase, brushless, IP23 with Automatic fast voltage regulator (output +/- 2% under normal condition), screen protected.
MANUAL PANEL CONTROL
DeepSea DSE6120 automatic controller inclusive of:
- Automatic mains failure (AMF)
- Automatic main circuit breaker
- Manual Change over switch with positions for
#MAIN-OFF-GENERATOR”
- Key button to start and stop the unit
- Emergency stop button
- Voltmeter (with selector switch #Phase to Zero-Phase to
Phase)
- Ampere meter
- Frequency meter
- Running hours counter
The manual panel controls engines and alternator parameters, providing the acoustic and visible alarms and shutdown of the equipment for critical parameters including low oil pressure, high engine temperature and over speed.
Sockets: CEE Type, one 3 poles and one 5 poles.
GENERAL FEATURES
The engine and the alternator are connected with a heavy-duty elastic coupling and are mounted on a common rigid base frame with anti-vibration dampers and lifting eyes flexible for transportation. The engine, alternator, fuel tank and panel are one integrated unit and mounted on skid.
ACCESSORIES
- Full and detailed operating and service manual (full workshop documentation for both motor and alternator) in English
- Spare parts catalogs, drawings and information concerning the foundation, erection requirements, electrical connections to load and earth, all in English - Tools kit (including pipe spanners for injector’s)
- Spare parts for 2000 hours of operation consisting: 4 oil filters, 4 main air filters, 4 safety air filters, 4 fuel filters, 2 cylinder gasket head covers.
- Full set of replacement switches and sensors.
General Description:
A complete diesel generator set including diesel engine, alternator, control panel, starting equipment, fuel tank and all other accessories for autonomous operation.
Factory test must be produced for any ordered units and all generators must be in accordance with international standards.
Technical Specifications:
Generator set,diesel,air cooled, 25kVA, 60Hz**
Rated Power
25kVA, 20KW, 220V Phase to Phase, 127V Phase to Neutral, 3 Phase
60Hz
Notes:
1.The ratings above are at (NTP) Normal Temperature and Pressure.
2.Power factor (Cos. = 0.8 )
3.Quoted output ratings are Prime power in accordance with ISO8528 e.g. power available at variable load with no limitation on hours of operation and capable of 10% overload for 1 hour in any 12 hours.
Engine
Heavy duty diesel engine, with the following characteristics:
Air cooled
- Synchronous speed: Up to 1800 rpm
- Speed governor
- Heavy duty air cartridge filter
- Cartridge oil filter
- External fuel filter
- Residential silencer
- Exhaust with suitable flexible piping
- Starter including batteries, leads and automatic battery
charging equipment
Fuel tank:
Integrated fuel tank of suitable construction having sufficient capacity to run the generator continuously for 8 hours at rated capacity. Tank to have all necessary piping for operation and filling and conveniently positioned fuel level indicator.
Alternator
- Synchronous, air cooled and brushless.
- Protection Class IP 23
- Automatic fast voltage regulator, maintaining the output
within 2 % under normal conditions
- Screen protected
- CEE Sockets: one 3 pole and one 5 pole
Panel board
- Automatic main circuit breaker
- Change over switch w/positions for:"MAINS"-"OFF"-"GENERATOR"
- Key to start and stop the unit
- Emergency stop button
- Meters for: Volts (with selector switch to show phases to zero and phase to phase voltages), amperes (three meters (one per phase) or one meter with selector switch for successive reading of phase apms, frequency, running hours counter
- Acoustic and visible alarms for critical parameters including high engine temperature and low oil pressure
Protection
The generator set should be equipped with automatic shutdown equipment if fatal parameters are exceeded including low oil pressure, high engine temperature and over-speed.
Mounting
The engine and the alternator should be connected with a heavy-duty elastic coupling and should be mounted on a common rigid base frame with anti-vibration dampers and lifting eyes flexible for transportation. Engine, alternator, fuel tank and panel should be one integrated unit mounted on skid.
Accessories: mandatory to be quoted for each item as stated below
1. Operation and maintenance manuals (full workshop documentation for both motor and alternator)
2. Spare parts catalogs, drawings and information concerning the foundation, erection requirements, electrical connections to load and earth, etc. all in English
3. Tools kit including pipe spanners for injector's etc.
4. Spare parts for 2000 hours of operation in the first two years as recommended by the engine manufacturers a minimum and including: oil filter, air filter cartridges, full sets of v-belts and 1 full set of cylinder head gaskets) please specify quantities
5. Full set of replacement switches/ sensors for detection of fatal parameters (low oil pressure, high engine temperature, belt failure etc.)
• Compra de 50 Generadores de Energía diesel, air cooled, POWER SOLUTIONS referencia P27D6, cabina insonora anti-robo, trifásica, certificada RETIE que cumplan con las siguientes características y estándares técnicos: Planta eléctrica AGG POWER SOLUTIONS referencia P27D6, cabina insonora anti-robo, trifásica, certificada RETIE, compuesta por:
- Motor diésel PERKINS referencia 404D-22G, 24.3 KWm a 1800 rpm, 4 tiempos, 4 cilindros en línea, 2.22 litros, relación de compresión 23.3:1, aspiración natural, enfriado por agua, gobernador de velocidad mecánico, precalentador con termóstato regulable, sistema de arranque eléctrico, legislación de emisiones Tier 4. - Generador STAMFORD referencia PI144D, sincrónico, 4 polos, sin escobillas, auto-excitado, AVR regulación de tensión ± 1%, aislamiento clase H, protección IP23, factor de potencia 0.8, 220 voltios, con resistencia anticondensación para devanados. - Controlador electrónico ComAp referencia InteliLite AMF25, puertos de comunicaciones RS232/RS485, puede ser monitoreado a través de los protocolos de comunicación TCP/IP SNMP y TCP/IP MODBUS de forma remota, incluye tarjeta ComAp CM-4G-GPS para comunicación GPRS por Simcard, selector de arranque automáticomanual, indicación de parámetros de operación, parada manual de emergencia, parada automática por fallas con alarmas. Incluye 8 contactos secos para monitoreo de alarmas. - Cabina insonora original de fábrica antirrobo: Nivel de ruido a 65 ± 2 dBA a 7 metros (protocolo de campo abierto), con botón externo de parada de emergencia, con selector manual de tres posiciones (manual/paro/automático) para operación alterna en caso de no operación del controlador electrónico AMF25. Fabricada en acero calibre 14, Incluye dispositivos de seguridad antirrobo como (ver Hoja Técnica anexa): puertas con bisagras antirrobo donde no se puede destornillar por fuera. Sensor de alarma instalado en puertas. Con 10 perforaciones en la base para anclaje de planta en sitio. No incluye la resistencia calefactora de ambiente. Dimensiones: 2.23Lx1.10Wx1.76H mts. Peso seco 1100 Kg.
Lugares de entrega:

1-Montecristo, Bolívar 1-San Jacinto del Cauca, Bolívar 1-Güicán, Boyacá 1-Iza, Boyacá 1-Paya, Boyacá 1-Pisba, Boyacá 1-Cartagena del Chairá, Caquetá 1-Florencia, Caquetá 1-La Montañita, Caquetá 1-Puerto Milán, Caquetá 1-Solano, Caquetá1-Almaguer, Cauca 1-San Sebastián, Cauca 1-Santa Rosa, Cauca 1-Chiriguaná, Cesar 1-El paso-Corregimiento de La Loma, Cesar 1-Pelaya, Cesar 1-Valledupar, Cesar 1-Bajo Baudó, Chocó 1-Bojayá, Chocó 1-Lloró, Chocó 1-Quibdó, Chocó 1-Quibdó, Chocó 1-Planeta Rica, Córdoba 1-Cogua, Cundinamarca 1-Facatativá, Cundinamarca 1-Fusagasugá, Cundinamarca 1-El Retorno, Guaviare 1-San José del Guaviare, Guaviare 1-Campoalegre, Huila 1-Neiva, Huila 1-El Piñón, Magdalena 1-Zapayán, Magdalena 1-Francisco Pizarro, Nariño 1-Mosquera, Nariño 1-Santa Bárbara, Nariño 1-Calarcá, Quindío 1-Córdoba, Quindío 1-Filandia, Quindío 1-Pijao, Quindío 1-Mistrató, Risaralda 1-Santuario, Risaralda 1-Buenavista, Sucre 1-El Roble, Sucre 1-San Antonio de palmito, Sucre 1-San Juan de Betulia, Sucre 1-Prado, Tolima 1-Santa Isabel, Tolima 1-Villahermosa, Tolima 1-Puerto Carreño, Vichada
• Distribución en cincuenta (50) entidades de salud de municipios priorizados relacionados previamente en los lugares de entrega.
• Instalaciones de los generadores de energía. En el alcance de la contratación se debe tener en cuenta todas las instalaciones y acometidas eléctricas que se requieran para poder entrar en funcionamiento y puesta en marcha de los nuevos equipos, así como las garantías.
• Capacitación al personal sobre operación, detección de fallas, rutinas diarias, medidas de seguridad, mantenimientos preventivos y todas las labores requeridas para la operación segura de los equipos instalados. Esta capacitación se desarrollará en las instalaciones de las entidades de salud al personal del área de mantenimiento asignadas para tal fin.
El pago se hará contra entrega, instalación y capacitación del personal en el uso de los generadores eléctricos.
d. Actividades específicas a ser completadas para el alcance de los objetivos Entrega de máximo 50 Generadores de Energía diesel,air cooled, 25kVA, 60Hz o POWER SOLUTIONS referencia P27D6 , manteniendo altos estándares de calidad y oportunidad en la entrega. e. Productos tangibles y medibles de la contratación
Producto, tiempo y %
Descripción del producto y Entregable
Producto 1:
Entrega, instalación de los Generadores de Energía diesel,air cooled, 25kVA, 60Hz, en los destinos acordados, incluida la capacitación del personal del uso y mantenimiento preventivo

Tener en cuenta las siguientes consideraciones para aplicar a la convocatoria:

  • Enviar propuesta a nombre de: Fondo de las Naciones Unidas para la Infancia
  • Las dos propuestas: Técnica y económica se deben enviar por separado.
  • Las propuestas se deben enviar con el asunto “RFQ2022-45 Generadores de Energía”. al correo electrónico col-corporateproposals@unicef.org.
  • Sólo se tendrán en cuenta las propuestas enviadas al correo electrónico col-corporateproposals@unicef.org ; No se consideran como válidas las propuestas que sean enviadas a funcionarios de UNICEF.
  • Cronograma de proceso:
    • Fecha límite de cotización: 13 de noviembre del 2022
  • Para poder aplicar a la convocatoria las empresas se deben registrar en la base de datos de proveedores de Naciones Unidas. Para registrarse de clic aquí (Número UNGM) el instructivo lo encuentra aquí
  • Enviar:
    • Certificado de existencia y representación legal / Cámara de comercio (No mayor a 30 días)
    • Copia de cédula del representante legal
    • Rut
    • Certificación bancaria (No mayor a 30 días)
  • Se solicita no enviar información adicional a la requerida en la convocatoria.